Inline Booster Pump Systems (continued)

9.

Controls-Soft Starters and VFDs: Reduced voltage starters and variable speed drives (inverter drives) may be used with Franklin three-phase submersible motors to reduce starting current, upthust, and mechanical stress during start-up. The guidelines for their use with submersible motors are different than with normal air cooled motor applications. Refer to the Franklin Electric Application, Installation and Maintenance (AIM) Manual Reduced Voltage Starters section or Variable Speed Submersible Pump Operation, Inverter Drives sections for specific details including required filtering.

10.

Motor Overload Protection: Submersible motors require properly sized ambient compensated Class 10 quick-trip overloads per Franklin’s AIM Manual guidelines to protect the motor. Class 20 or higher overloads are NOT acceptable. Franklin’s SubMonitor is strongly recommended for all large submersibles since it is capable of sensing motor heat without any additional wiring to the motor. Applications using Soft Starters with a SubMonitor require a start-up bypass - consult the factory for details. SubMonitor can not be used in applications using a VFD control.

11.

Motor Surge Protection: Properly sized, grounded and dedicated motor surge arrestors must be installed in the supply line of the booster module as close to the motor as possible. This is required on all systems including those using soft-starters and variable speed drives (inverter drives).

12.

Wiring: Franklin’s lead assemblies are only sized for submerged operation in water to the motor nameplate maximum ambient temperature and may overheat and cause failure or serious injury if operated in air. Any wiring not submerged must meet applicable national and local wiring codes and Franklin Cable Chart Table 24. (Notice: wire size, wire rating and insulation temperature rating must be known when determining its suitability to operate in air or conduit. Typically, for a given size and rating, as the insulation temperature rating increases, its ability to operate in air or conduit also increases.)

13.

Check Valves: Spring-loaded check valves must be used on start-up to minimize motor upthusting, water hammer, or in multiple booster (parallel) applications to prevent reverse flow.

14.

Pressure Relief Valves: A pressure relief valve is required and must be selected to ensure that, as the pump approaches shut-off, it never reaches the point that the motor will not have adequate cooling flow past it.

15.

System Purge (Can Flooding): An air bleeder valve must be installed on the booster sleeve so that flooding may be accomplished prior to booster startup. Once fl ooding is complete, the booster should be started and brought up to operating pressure as quickly as possible to minimize the duration of an upthust condition. At no time should air be allowed to gather in the booster sleeve because this will prevent proper cooling of the motor and permanently damage it.

16.

System Flush – Must Not Spin Pump: Applications may utilize a low flow flushing operation. Flow though the booster sleeve must not spin the pump impellers and the motor shaft. If spinning takes place,the bearing system will be permanently damaged and the motor life shortened. Consult the booster pump manufacturer for maximum flow rate though the pump when the motor is not energized.

Table 37 Franklin cable chart (see 12 Wiring)
Cable Temp.Rating
(ºC )
Motor Nameplate
Rated Amps
Full Load
#10 AWG #8 AWG #6 AWG #4 AWG #2 AWG Source of Cable Ampacity
In Air In
Conduit
In Air In
Conduit
In Air In
Conduit
In Air In
Conduit
In Air In
Conduit
75 3-Lead (DOL) 40A 28A 56A

40A

76A 52A 100A 68A 136A 92A US N.E.C.,2002 edition,
Tables 310.16 &310.17
6-Lead (Y-) 69A 48A 97A 69A 132A 90A 173A 118A 236A 159A
90 3-Lead (DOL) 44A 32A 64A 44A 84A 60A 112A 76A 152A 104A US N.E.C.,2002 edition,
Tables 310.16 &310.17
6-Lead (Y-) 76A 55A 111A 76A 145A 104A 194A 132A 263A 180A
135 3-Lead (DOL) 63A 46A 74A 51A 104A 74A 145A 98A 185A 126A Standard AAR (American Association of Railroads)
RP-585
6-Lead (Y-) 109A 80A 127A 88A 180A 129A 251A 170A 320A 219A
Based on 30 °C maximum ambient with cable length of 100 feet or less.
 
Pages 31-35 36 37 38 39 40 Pages 41-45
"Left click" to VIEW pdf. To SAVE pdf "Right Click" & choose
Page 36 | Page 38     
 
 
  Home     Corporate     Water Systems     Fueling Systems     International  
  TOP  

Copyright 1998-2004.  Please review our Terms of Use before accessing this site.
Franklin Electric Co., Inc.        400 E. Spring St.,  Bluffton,  IN,  46714,  U.S.A.
E-mail: webmaster@fele.com               Tel: 260.824.2900           Fax: 260.824.2909