| Fault Message |
Problem / Condition |
Possible Cause |
| SF Amps Set Too High |
SF Amps setting above 359 Amps |
Motor SF Amps not entered |
| Phase Reversal |
Reversed incoming voltage phase sequence |
Incoming power problem |
| Under Load |
Normal line current |
Wrong SF Max Amps setting |
| Low line current |
Over pumping well Clogged pump intake Closed Valve Loose pump impeller Broken shaft or coupling Phase loss |
| Over Load |
Normal line current |
Wrong SF Max Amps setting |
| High line current |
High or low line voltage Ground fault Pump or motor dragging Motor stalled or bound pump |
| Overheat |
Motor temperature sensor has deteced excess motor temperature |
High or low line voltage Motor is overloaded Excessive current unbalance Poor motor cooling High water temperature Excessive electrical noise (VFD in close proximity) |
| Unbalance |
Current difference between any two legs exceeds programmed setting |
Phase loss Unbalanced power supply Open delta transformer |
| Overvoltage |
Line voltage exceeds programmed setting |
Unstable power supply |
| Undervoltage |
Line voltage below programmed setting |
Poor connection in motor power circuit Unstable or weak power supply |
| False Starts |
Power has been interrupted too many times in a 10 second period |
Chattering contacts Loose connections in motor power circuit Arcing contacts |