| |
| |
 |
 |
| Franklin Application/Installation Data
(AID) ... For The Professional Driller-Installer |
Vol. 16, No. 1 January/February
1998 |
|
| |
| CONTACTOR COIL
CHARACTERISTICS |
| |
| The following issue of Franklin Aid
is an expanded and updated version of our November/December 1988 issue.
This information is repeated in response to several inquires made
to our Hotline personnel.
Single-phase deluxe control boxes and three-phase
pump panels typically have two distinct electrical circuits as shown
in Figure 1. First is the main line or motor power circuit. This
circuit normally runs from the main power disconnect to the motor,
through a contactor or starter. These systems also use a second
circuit typically known as a control loop or control circuit.
|
| |
 |
|
The control circuit
will include the magnetic coil of the contactor, power supply
for the control circuit and any number of control switches.
These control switches can be pressure switches, float switches,
timers, or any type of on/ off control device.
The magnetic coil of a contactor or starter
is similar to the coil in a potential or voltage relay. This
magnetic or "mag" coil consists of a series of wire wrapped
around a bobbin. When electricity is passed through this wire,
it creates an electromagnet. When properly energized, a moveable
contact or "point" is pulled together, closing a pump system's
non-nay open contacts. As the contacts close, main line or
motor supply current flows through the contacts to power the
motor. When the control circuit voltage is interrupted, the
coil de-energizes and the motor stops.
|
|
| |
| Magnetic coils, whether in a single-phase
contactor or in a three-phase pump panel, are single-phase devices.
Control circuit coil voltage can be supplied from either inside the
control box/pump panel or from a source outside the box. In either
case the control circuit supply voltage must match the coil's rated
voltage. Note: control circuit coil voltage does not have to equal
main line power voltage. Step-down transformers are commonly used
in control circuits.
Magnetic coil specifications typically use terminology
like rated voltage, pick-up voltage, sealing voltage (a.k.a. hold-in
voltage), and drop-out voltage. Rated voltage is coil supply voltage
and must match the control circuit power source. Coils are found
in common supply voltages (i.e. 480, 240, 120 volts) and can also
be found using low voltage (i.e. 24 volts). Pick-up voltage is the
amount of voltage required to overcome the mechanical forces, like
gravity and spring tension, trying to keep the contacts from moving
together or closing. Sealing voltage or hold-in voltage is the amount
of voltage needed to maintain the contacts in their new, typically
closed, position after pick-up voltage is reached. Sealing voltage
is normally less than pick-up voltage. Drop-out voltage is the amount
of voltage below which the magnetic field becomes too weak to overcome
the mechanical forces trying to return the contacts to their at-rest
position. An important point about contactor coils, is that most
of them will overheat and can burnout if subjected to either abnormally
high or low voltage. Figure 2 shows operating characteristics
of a typical contactor. The National Electric Manufacturers Association
(NEMA) requires that standard magnetic control devices operate satisfactorily
between 85% and 110% of rated voltage, and many contactors have
lower sealing voltages. However, most coils will begin to overheat
and may burnout when the current (amps) exceeds 110% of rated current
at rated voltage. If the contacts are open, this current can be
exceeded at a voltage well below either pick-up or sealing voltage.
|
| |
Figure 2. |
| |
| In the next issue of Franklin Aid we will continue
our discussion on "Contactor Coil
Characteristics" |
| |
|
|