Water Systems


SubMonitor


SubMonitor Troubleshooting

Fault Message Problem / Condition Possible Cause
SF Amps Set Too High SF Amps setting above 359 Amps Motor SF Amps not entered
Phase Reversal Reversed incoming voltage phase sequence Incoming power problem
Under Load Normal line current Wrong SF Max Amps setting
Low line current Over pumping well
Clogged pump intake
Closed Valve
Loose pump impeller
Broken shaft or coupling
Phase loss
Over Load Normal line current Wrong SF Max Amps setting
High line current High or low line voltage
Ground fault
Pump or motor dragging
Motor stalled or bound pump
Overheat Motor temperature sensor has deteced excess motor temperature High or low line voltage
Motor is overloaded
Excessive current unbalance
Poor motor cooling
High water temperature
Excessive electrical noise
(VFD in close proximity)
Unbalance Current difference between any two legs exceeds programmed setting Phase loss
Unbalanced power supply
Open Delta transformer
Overvoltage Line voltage exceeds programmed setting Unstable power supply
Undervoltage Line voltage below programmed setting Poor connection in motor power circuit
Unstable or weak power supply
False Starts Power has been interrupted too many times in a 10 second period Chattering contacts
Loose connections in motor power circuit
Arcing contacts