Safety Features
The Fluke 179 Series DMM has been designed to meet the IEC-1010
standards. Which means it is designed to protect you against transients
in three-phase distribution systems, including:
- Equipment in fixed installations, such as switch gear and polyphase motors.
- Bus and feeder in industrial plants.
- Single-phase commercial lighting.
|
| Specifications
|
| AC Amps
|
Range: 3 mA to 10.00A (20A overload for 30 seconds)
Accuracy: ± (1.5% of reading plus 3 counts)
Crest Factor: £3
AC Response: 45 Hz to 1 kHz
|
| DC Amps
| Range: 0.01mA to 10.00A (20A overload for 30 seconds)
Accuracy:± (1.0% of reading plus 3 counts)
|
| AC Volts
| Range: 30 mV to 1000V
Accuracy: 45 Hz to 500 Hz 1% of rdg + 3 counts, 500 Hz to 1 kHz 2% of rdg + 3 counts
AC Response: 45 Hz to 1 kHz
|
| DC Volts
| Range: 0.1 mV to 1000V
Accuracy: ± (0.09% of reading plus 2 counts)
|
| Resistance
|
Range: 0.1W to 50.00 MW
Best Accuracy: ± (0.9% of reading plus 1 count)
|
| Capacitance
| Range: 1 nF to 9999 µF
Best Accuracy: ± (1.2% of reading plus 2 counts)
|
| Continuity
| Beeper guaranteed on <25W, guaranteed off >250W; detects opens or shorts of 250 µs or longer
|
| Frequency
|
Range: Voltage Input: 2 Hz to 100 kHz / Current
Input: 2 Hz to 30 kHz
Accuracy: ± (0.1% of reading plus 1 count)
|
| Temperature |
Range: -40ºC to +400ºC, -40ºF to +752ºF
Accuracy:1% + 1.0 ºC, 1% + 1.8 ºF
|
|